Skip to main content
Skip to main content
Product title:

Quadra-Fire Castile & Sante Fe Snap Disc #2 Safety Switch (L250-95): SRV7000-268-AMP

Product rating:
Product price:
$14.99

A $45.00 Savings over the OEM

Product SKU ! SRV7000-268-AMP
Product MPN ! SRV7000-268
Product availability: In Stock
Bullet point features

Frequently Bought Together

Description

Snap Disc #2 (Fuel Delivery Interrupt) L250°-95, Auto Reset

Snap disc #2 is also located on the backside of the feed drop tube. There are 2 orange wires connected to it. This snap disc will turn off the feed system which will turn off the appliance if an overfire/ overheat condition should occur or if the convection blower should fail to move enough air through the heat exchanger to cool the stove and keep it from overheating. If an event occurs that activates this switch snap disc will cut the power to the feed motor when the switch senses a surface temperature of 250°F or more. As the stove cools itself down, the switch will return to a normally closed position at 155°F.

This part is also known as a thermodisc, bi-metal switch, or snap switch.


     


    Replacement For Part Number:

    • SRV7000-268

    View Compatible Models

    UPC: 652174479481

    Compatible Models

      Quadra-Fire

    • Castile F/S (Post: 0071195663)
    • Castile FS MBK
    • Castile Insert
    • Santa Fe B
    • Santa Fe MBK
    • Santa Fe
    • Santa Fe-C INS

    Technical Specs

    Instructions

    Install Instructions For Quadra-Fire Castile & Sante Fe Snap Disc #2 Safety Switch (L250-95): SRV7000-268-AMP

    Troubleshooting snap disc #2 - Symptom, Not Feeding


    1. Unplug unit
    2. Locate snap disc #2 behind the right side service panel of the stove or insert
    3. Remove the orange and black wires from the switch and connect them together with a jumper wire
    4. Restart unit
    5. If the unit starts to feed, replace the switch
    6. If the unit does not start feeding after 2 minutes running, test the switch for a normally closed position at room temperature, if you have continuity, the problem is not snap disc #2.

    Castile and Sante Fe are basically the same stove, the troubleshooting manual is the same for both.

    Troubleshooting

    Troubleshooting Quadrafire Pellet Stoves: Not Feeding Pellets

     

    Snap Discs

     

    Snap discs are used in a variety of ways and have many names, such as; Thermodiscs, Thermal switch, Bi-metal Switches, Fan Switches, Limit Switches, High Limit Switches, Low Limit Switches and Proof of Fire Switches. These switches have two or more wire terminals and inside the switch there is a disc that is coated with two dissimilar metals. Because all metals expand and contract at different temperatures, the surface tension of these metals together on a circular sheet of metal causes the disc to either have a convex or concave shape. Depending on which side of this disc is facing up toward the pin, the switch is either making a normally open or closed circuit at room temperature. When the switch detects heat, the metal on the disc will expand causing the disc to “flip” its convex or concave shape which allows the pin inside the switch to reverse its normally open or closed state. Bi-metal snap discs will automatically reset back to their normal state when enough of a temperature change is detected. Singular metal snap discs will have a button on the switch that must be manually pressed to reset the switch.

     

    Most Quadrafire pellet stoves use 3 snap discs to control or monitor functions of the stove and are referenced as Snap Disc #1, #2 and #3 for most models. Models include the now obsolete 800, 1000, 1100i Insert, Mt Vernon OM (original model) and the Contour as well as current models still in production which are the Santa Fe, Santa Fe Insert, Castile, Castile Insert, CB1200 and CB1200i Insert.

     

    The Mt Vernon AE. Mt Vernon E2, Edge 60 and the Trekker use a completely different set of controls but do have a drop tube power safety shutoff which is similar in function to Snap Disc #3. On these models, this is the ONLY snap disc that is used.

     

    Troubleshooting Snap Disc #1

     

    Snap Disc #1 (Convection Blower Power ON/ OFF) is usually located on the right side of the appliance. But it can be on the left side on some models. Models made after 2002 will all have 2 purple wires connected to it. This switch is going to power up the convection room air blower. This switch is always normally open, meaning that the blower circuit is not receiving power at room temperature.

     

    Power is always present at snap disc #1 if the unit is plugged in regardless if the stove is running or not. This snap disc is not part of the feed motor circuit but if this switch fails to close, the stove or insert will overheat which would then trigger Snap Disc #2 to open the feed circuit and shut down the stove or insert.

     

    • If the room blower is not coming on and the stove is overheating, unplug the stove, bypass snap disc #1 by connecting a jumper wire to the two purple wires and plug the stove back into the outlet. The blower should come on even if the stove is cold. If the blower does not come on, replace the blower.
    • To test the switch, test for continuity across the terminals of the switch at room temperature. There should be no signal. If there is, replace the switch.
    • If there is no signal at room temperature, heat the bottom surface of the switch with an open flame or heat gun, the switch should close after a few seconds for a closed circuit. If there is no closed circuit, replace the switch.

     

    Notes: 

    • If snap disc #1 malfunctions the room blower is either on at start-up, which it shouldn’t be or the room blower never receives power and causes the stove to overheat. If the unit isn’t feeding at startup, snap disc #1 is not the problem.
    • Snap disc #1 is located in different places on each model and will have different temperature values from one model to the next. Make sure you are ordering the correct snap disc #1 for your model.

     

    Troubleshooting Snap Disc #2

     

    Snap Disc #2 is always used to cut power to the feed circuit if an overheating situation occurs. Overheating usually happens when the convection room air blower fails to power up, either because the blower is bad or because snap disc #1 is open or fails to close. 

     

    An overheat event can also happen if the room air blower is excessively dirty or the blower is spinning slower than it should be for the user’s designated heat level output. For example: the blower is worn out and is not spinning at full speed even when full power is sent to the blower. Though it’s not common, overheating can occur if the stove, vent or vent cap is excessively dirty or restricted in some way.

     

    Snap disc #2 is mounted in a variety of places depending upon your model and can be used in two different ways to achieve the same result.

     

    If you have yellow wires at Snap Disc #2 It is being used indirectly to shut the feed system down as a “Thermostat Override Switch”.

     

    Owner’s manuals refer to this switch as the “Thermostat Override” but not all models truly use the switch to override the thermostat circuit. If the wires on your snap disc #2 are any other color than yellow, skip to the next bold section below.

     

    By interrupting the thermostat’s 18 volt circuit (opening the circuit), the demand for heat is interrupted and the fire will subside or go out. When this switch is used in this way, the switch will automatically reset when the unit cools back to a safe operating temperature, assuming that the thermostat is still calling for heat.

     

    When snap disc #2 is used in this way and the unit is not feeding pellets at start-up, you must verify that the thermostat is calling for heat. When the TSTAT is calling for heat the circuit will be closed at both the thermostat AND the at snap disc #2. This is verified when the red call light on the junction box is illuminated. If the red call light is “ON”, snap disc #2 is closed.

     

    • If the thermostat is calling for heat and the red call light is not illuminated; 1. If snap disc #2 is an automatic reset switch (no button to press for a manual reset), bypassing the switch with a jumper wire will close the circuit and the red call light should come on. If this happens, replace snap disc #2. If the light still doesn’t come on, the TSTAT connection may be faulty. Connect a wire across the TSAT terminals at the stove, if the light comes on, replace the thermostat, the thermostat wire or both.

    • If snap disc #2 has a reset button, make sure the thermostat is calling for heat and reset the switch by pushing in on the button. You should hear a “click”. If the snap disc was in the open position the red call light should come “ON” and the stove should begin to startup.

     

    If you have any other color wire connected to snap disc #2 other than yellow, this switch is going to be wired in series with other safety switches within the 120 volt feed system circuit. Testing all of these switches may be required for proper troubleshooting.

     

    If the wires on your stove or insert are NOT yellow, snap disc #2 is being used to open the 120 volt circuit directly to the auger feed motor. Depending upon the model, the wires on your unit will either be orange and black, red and black, red and orange or just two black wires. When snap disc #2 is used in this way, the switch is going to be a manual reset switch. Using your Owner’s manual, locate snap disc #2 and press in on the button between the wires. You should hear a “click”. If your stove is “ON” and calling for heat, feeding should resume.

    

    Troubleshooting Snap Disc #3 (Emergency Power Shutdown Switch) 

     

    Snap disc #3 is always located on the feed tube under the hopper in the back of the unit. This switch will always have gray wires attached to it if the unit was made after 2002. Some models will have gray wires that actually look sort of brownish. Snap disc #3 is ALWAYS a manual reset switch and is designed to kill power to the entire unit if a temperature of 250°F or more is detected in the feed tube leading back to the hopper.

     

    This switch is normally closed to allow 120 volts to come in from the power outlet to the junction box control and wiring harness. When this switch is open it can be reset by pushing in on the button between the two gray/ brownish wires. If the switch fails to reset the stove will not receive any power and will need to be replaced. Likewise, if the switch is not staying closed and is opening up and random times, the switch should be replaced.

     

    If this switch is triggered by an actual overheating event, a professional may need to be called in to repair the stove as there will likely be other damage taken to the feed motor or other parts of the stove.

     

    Note: Manual reset snap discs, whether they are used as snap disc #2 or snap disc #3 are notorious for opening during power surge events simply by being plugged into the power outlet. The stove doesn’t even have to be “ON” for this to happen. If your stove isn’t working after some time of not using it this is most likely the problem.




    Warranty

    Unfortunately, sometimes products do not work like they are supposed to. We offer a 90 day warranty on manufacturer defects. Some manufacturers make this a very simple and easy process unfortunately others do not. Items must be used in accordance with the manufacturers guidelines to qualify for warranty replacement. Please be advised that warranty claims for these parts may take up to 4 weeks for processing, and customers must cover shipping.

    Shipping Information

    This Item Qualifies For Free Shipping With Orders Over $49!

    HOLIDAY UPDATE
    Due to the upcoming Christmas and New Years holidays, shippers will not be picking up on the dates below. Additionally, packages may take longer to arrive than expected. We appreciate your understanding and patience during this time.

    • USPS: No pickup on Dec 24th, Dec 25th, and Jan 1st.
    • UPS: No pickup on Dec 24th (except NDA and 2nd Day), Dec 25th, Dec 31st (except NDA and 2nd Day), and Jan 1st.
    CANADA UPDATE

    Due to the ongoing Canada Post postal workers' strike, we are forced to suspend all ordering to Canada. Please be advised that any shipments that did not clear U.S. customs by November 15th will be delayed until Canada Post is fully operational. We appreciate your understanding and patience during this time.

    When Will My Order Ship?

    All orders are typically processed within 24 hours of receiving payment and are shipped from us same day if placed before our shipping cutoff time (Monday - Friday: 12PM, Saturday: 10AM, Sunday: No Shipping), orders placed after our cutoff time are shipped the next morning.

    Do You Offer Express Shipping?

    Yes! Please note the shipping times are based on business days, weekends and holidays do not count to the delivery date. Please see our expedited ship time schedules here.

    How Does Free Shipping Work?

    Most orders over $49 qualify for free shipping! Orders which ship for free are shipped with either USPS or UPS based on our discretion. If you are using a PO box, free shipping orders will always go USPS.

    Do You Ship To Canada?

    We ship to Canada! We estimate USPS to take 4-10 days once receiving your package from us. We do not offer expedited shipping of any kind to Canada. Please allow an extra 2-5 days for all shipments to Canada. Free shipping is not available to Canada.

    Do You Ship To Alaska Or Hawaii?

    We ship to both Alaska and Hawaii! We do not offer next day or two day shipping to Alaska or Hawaii. Free shipping is not available to Alaska or Hawaii.

    Do You Ship Outside The US Or Canada?

    Unfortunately, at this time we do not offer international shipping other than to Canada.

    Shipping Time Estimations

    For information on shipping time estimations, see the Shipping Information & Transit Times on the shipping page.

    Learn More About Our Shipping Information
    Jump back to product information tab navigation

    Description

    Snap Disc #2 (Fuel Delivery Interrupt) L250°-95, Auto Reset

    Snap disc #2 is also located on the backside of the feed drop tube. There are 2 orange wires connected to it. This snap disc will turn off the feed system which will turn off the appliance if an overfire/ overheat condition should occur or if the convection blower should fail to move enough air through the heat exchanger to cool the stove and keep it from overheating. If an event occurs that activates this switch snap disc will cut the power to the feed motor when the switch senses a surface temperature of 250°F or more. As the stove cools itself down, the switch will return to a normally closed position at 155°F.

    This part is also known as a thermodisc, bi-metal switch, or snap switch.


       


      Replacement For Part Number:

      • SRV7000-268

      View Compatible Models

      UPC: 652174479481

      Compatible Models

        Quadra-Fire

      • Castile F/S (Post: 0071195663)
      • Castile FS MBK
      • Castile Insert
      • Santa Fe B
      • Santa Fe MBK
      • Santa Fe
      • Santa Fe-C INS

      Instructions

      Install Instructions For Quadra-Fire Castile & Sante Fe Snap Disc #2 Safety Switch (L250-95): SRV7000-268-AMP

      Troubleshooting snap disc #2 - Symptom, Not Feeding


      1. Unplug unit
      2. Locate snap disc #2 behind the right side service panel of the stove or insert
      3. Remove the orange and black wires from the switch and connect them together with a jumper wire
      4. Restart unit
      5. If the unit starts to feed, replace the switch
      6. If the unit does not start feeding after 2 minutes running, test the switch for a normally closed position at room temperature, if you have continuity, the problem is not snap disc #2.

      Castile and Sante Fe are basically the same stove, the troubleshooting manual is the same for both.

      Troubleshooting

      Troubleshooting Quadrafire Pellet Stoves: Not Feeding Pellets

       

      Snap Discs

       

      Snap discs are used in a variety of ways and have many names, such as; Thermodiscs, Thermal switch, Bi-metal Switches, Fan Switches, Limit Switches, High Limit Switches, Low Limit Switches and Proof of Fire Switches. These switches have two or more wire terminals and inside the switch there is a disc that is coated with two dissimilar metals. Because all metals expand and contract at different temperatures, the surface tension of these metals together on a circular sheet of metal causes the disc to either have a convex or concave shape. Depending on which side of this disc is facing up toward the pin, the switch is either making a normally open or closed circuit at room temperature. When the switch detects heat, the metal on the disc will expand causing the disc to “flip” its convex or concave shape which allows the pin inside the switch to reverse its normally open or closed state. Bi-metal snap discs will automatically reset back to their normal state when enough of a temperature change is detected. Singular metal snap discs will have a button on the switch that must be manually pressed to reset the switch.

       

      Most Quadrafire pellet stoves use 3 snap discs to control or monitor functions of the stove and are referenced as Snap Disc #1, #2 and #3 for most models. Models include the now obsolete 800, 1000, 1100i Insert, Mt Vernon OM (original model) and the Contour as well as current models still in production which are the Santa Fe, Santa Fe Insert, Castile, Castile Insert, CB1200 and CB1200i Insert.

       

      The Mt Vernon AE. Mt Vernon E2, Edge 60 and the Trekker use a completely different set of controls but do have a drop tube power safety shutoff which is similar in function to Snap Disc #3. On these models, this is the ONLY snap disc that is used.

       

      Troubleshooting Snap Disc #1

       

      Snap Disc #1 (Convection Blower Power ON/ OFF) is usually located on the right side of the appliance. But it can be on the left side on some models. Models made after 2002 will all have 2 purple wires connected to it. This switch is going to power up the convection room air blower. This switch is always normally open, meaning that the blower circuit is not receiving power at room temperature.

       

      Power is always present at snap disc #1 if the unit is plugged in regardless if the stove is running or not. This snap disc is not part of the feed motor circuit but if this switch fails to close, the stove or insert will overheat which would then trigger Snap Disc #2 to open the feed circuit and shut down the stove or insert.

       

      • If the room blower is not coming on and the stove is overheating, unplug the stove, bypass snap disc #1 by connecting a jumper wire to the two purple wires and plug the stove back into the outlet. The blower should come on even if the stove is cold. If the blower does not come on, replace the blower.
      • To test the switch, test for continuity across the terminals of the switch at room temperature. There should be no signal. If there is, replace the switch.
      • If there is no signal at room temperature, heat the bottom surface of the switch with an open flame or heat gun, the switch should close after a few seconds for a closed circuit. If there is no closed circuit, replace the switch.

       

      Notes: 

      • If snap disc #1 malfunctions the room blower is either on at start-up, which it shouldn’t be or the room blower never receives power and causes the stove to overheat. If the unit isn’t feeding at startup, snap disc #1 is not the problem.
      • Snap disc #1 is located in different places on each model and will have different temperature values from one model to the next. Make sure you are ordering the correct snap disc #1 for your model.

       

      Troubleshooting Snap Disc #2

       

      Snap Disc #2 is always used to cut power to the feed circuit if an overheating situation occurs. Overheating usually happens when the convection room air blower fails to power up, either because the blower is bad or because snap disc #1 is open or fails to close. 

       

      An overheat event can also happen if the room air blower is excessively dirty or the blower is spinning slower than it should be for the user’s designated heat level output. For example: the blower is worn out and is not spinning at full speed even when full power is sent to the blower. Though it’s not common, overheating can occur if the stove, vent or vent cap is excessively dirty or restricted in some way.

       

      Snap disc #2 is mounted in a variety of places depending upon your model and can be used in two different ways to achieve the same result.

       

      If you have yellow wires at Snap Disc #2 It is being used indirectly to shut the feed system down as a “Thermostat Override Switch”.

       

      Owner’s manuals refer to this switch as the “Thermostat Override” but not all models truly use the switch to override the thermostat circuit. If the wires on your snap disc #2 are any other color than yellow, skip to the next bold section below.

       

      By interrupting the thermostat’s 18 volt circuit (opening the circuit), the demand for heat is interrupted and the fire will subside or go out. When this switch is used in this way, the switch will automatically reset when the unit cools back to a safe operating temperature, assuming that the thermostat is still calling for heat.

       

      When snap disc #2 is used in this way and the unit is not feeding pellets at start-up, you must verify that the thermostat is calling for heat. When the TSTAT is calling for heat the circuit will be closed at both the thermostat AND the at snap disc #2. This is verified when the red call light on the junction box is illuminated. If the red call light is “ON”, snap disc #2 is closed.

       

      • If the thermostat is calling for heat and the red call light is not illuminated; 1. If snap disc #2 is an automatic reset switch (no button to press for a manual reset), bypassing the switch with a jumper wire will close the circuit and the red call light should come on. If this happens, replace snap disc #2. If the light still doesn’t come on, the TSTAT connection may be faulty. Connect a wire across the TSAT terminals at the stove, if the light comes on, replace the thermostat, the thermostat wire or both.

      • If snap disc #2 has a reset button, make sure the thermostat is calling for heat and reset the switch by pushing in on the button. You should hear a “click”. If the snap disc was in the open position the red call light should come “ON” and the stove should begin to startup.

       

      If you have any other color wire connected to snap disc #2 other than yellow, this switch is going to be wired in series with other safety switches within the 120 volt feed system circuit. Testing all of these switches may be required for proper troubleshooting.

       

      If the wires on your stove or insert are NOT yellow, snap disc #2 is being used to open the 120 volt circuit directly to the auger feed motor. Depending upon the model, the wires on your unit will either be orange and black, red and black, red and orange or just two black wires. When snap disc #2 is used in this way, the switch is going to be a manual reset switch. Using your Owner’s manual, locate snap disc #2 and press in on the button between the wires. You should hear a “click”. If your stove is “ON” and calling for heat, feeding should resume.

      

      Troubleshooting Snap Disc #3 (Emergency Power Shutdown Switch) 

       

      Snap disc #3 is always located on the feed tube under the hopper in the back of the unit. This switch will always have gray wires attached to it if the unit was made after 2002. Some models will have gray wires that actually look sort of brownish. Snap disc #3 is ALWAYS a manual reset switch and is designed to kill power to the entire unit if a temperature of 250°F or more is detected in the feed tube leading back to the hopper.

       

      This switch is normally closed to allow 120 volts to come in from the power outlet to the junction box control and wiring harness. When this switch is open it can be reset by pushing in on the button between the two gray/ brownish wires. If the switch fails to reset the stove will not receive any power and will need to be replaced. Likewise, if the switch is not staying closed and is opening up and random times, the switch should be replaced.

       

      If this switch is triggered by an actual overheating event, a professional may need to be called in to repair the stove as there will likely be other damage taken to the feed motor or other parts of the stove.

       

      Note: Manual reset snap discs, whether they are used as snap disc #2 or snap disc #3 are notorious for opening during power surge events simply by being plugged into the power outlet. The stove doesn’t even have to be “ON” for this to happen. If your stove isn’t working after some time of not using it this is most likely the problem.




      Warranty

      Unfortunately, sometimes products do not work like they are supposed to. We offer a 90 day warranty on manufacturer defects. Some manufacturers make this a very simple and easy process unfortunately others do not. Items must be used in accordance with the manufacturers guidelines to qualify for warranty replacement. Please be advised that warranty claims for these parts may take up to 4 weeks for processing, and customers must cover shipping.

      Shipping Info

      This Item Qualifies For Free Shipping With Orders Over $49!

      HOLIDAY UPDATE
      Due to the upcoming Christmas and New Years holidays, shippers will not be picking up on the dates below. Additionally, packages may take longer to arrive than expected. We appreciate your understanding and patience during this time.

      • USPS: No pickup on Dec 24th, Dec 25th, and Jan 1st.
      • UPS: No pickup on Dec 24th (except NDA and 2nd Day), Dec 25th, Dec 31st (except NDA and 2nd Day), and Jan 1st.
      CANADA UPDATE

      Due to the ongoing Canada Post postal workers' strike, we are forced to suspend all ordering to Canada. Please be advised that any shipments that did not clear U.S. customs by November 15th will be delayed until Canada Post is fully operational. We appreciate your understanding and patience during this time.

      When Will My Order Ship?

      All orders are typically processed within 24 hours of receiving payment and are shipped from us same day if placed before our shipping cutoff time (Monday - Friday: 12PM, Saturday: 10AM, Sunday: No Shipping), orders placed after our cutoff time are shipped the next morning.

      Do You Offer Express Shipping?

      Yes! Please note the shipping times are based on business days, weekends and holidays do not count to the delivery date. Please see our expedited ship time schedules here.

      How Does Free Shipping Work?

      Most orders over $49 qualify for free shipping! Orders which ship for free are shipped with either USPS or UPS based on our discretion. If you are using a PO box, free shipping orders will always go USPS.

      Do You Ship To Canada?

      We ship to Canada! We estimate USPS to take 4-10 days once receiving your package from us. We do not offer expedited shipping of any kind to Canada. Please allow an extra 2-5 days for all shipments to Canada. Free shipping is not available to Canada.

      Do You Ship To Alaska Or Hawaii?

      We ship to both Alaska and Hawaii! We do not offer next day or two day shipping to Alaska or Hawaii. Free shipping is not available to Alaska or Hawaii.

      Do You Ship Outside The US Or Canada?

      Unfortunately, at this time we do not offer international shipping other than to Canada.

      Shipping Time Estimations

      For information on shipping time estimations, see the Shipping Information & Transit Times on the shipping page.

      Learn More About Our Shipping Information

      Customer Reviews

      Based on 4 reviews
      100%
      (4)
      0%
      (0)
      0%
      (0)
      0%
      (0)
      0%
      (0)
      J
      Jeff R.
      Timely

      I have placed 2 orders for a total of 4 parts for my Quadra-fire pellet stove. Each part was accurate and the delivery was very quick. The email communication was great as well. Will be ordering from this vendor again.

      C
      Craig W.
      Pellet Stove Parts

      In the beginning of every heating season I buy parts to my Quadra-Fire Castile insert pellet stove to have on hand parts to replace / repair if needed. Stove & Grille parts for less is my go to place. Always they come thru with a timely turnaround and large inventory on hand.

      m
      matthew p.
      snap disc

      great transaction

      J
      James A.M.

      Quadrafire Snap Disc #2 (250-95F), SRV7000-268-AMP

      QUESTIONS & ANSWERS

      If your question does not concern this specific product, use our contact form

      Have a Question?

      Be the first to ask a question about this.

      Ask a Question

      Customer Reviews

      Based on 4 reviews
      100%
      (4)
      0%
      (0)
      0%
      (0)
      0%
      (0)
      0%
      (0)
      J
      Jeff R.
      Timely

      I have placed 2 orders for a total of 4 parts for my Quadra-fire pellet stove. Each part was accurate and the delivery was very quick. The email communication was great as well. Will be ordering from this vendor again.

      C
      Craig W.
      Pellet Stove Parts

      In the beginning of every heating season I buy parts to my Quadra-Fire Castile insert pellet stove to have on hand parts to replace / repair if needed. Stove & Grille parts for less is my go to place. Always they come thru with a timely turnaround and large inventory on hand.

      m
      matthew p.
      snap disc

      great transaction

      J
      James A.M.

      Quadrafire Snap Disc #2 (250-95F), SRV7000-268-AMP

      Liquid error (layout/theme line 255): Could not find asset snippets/iStock-notify-me.liquid